Siemens 5SU1326-7FP06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1326-7FP06 SENTRON RCBO, 2P C-curve 6A, 6kA

MPN5SU1326-7FP06
Active

Siemens SENTRON RCBO, 2-pole, C-curve, 6 A rated at 30 °C, 6 kA per EN 60898, 7.5 kA per IEC 60947-2, 2 MW width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SU1326-7FP06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1326-7FP06 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1326-7FP06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum70 °C
Minimum-40 °C
Width36 mm
Height85 mm
Depth72 mm
Installation depth70 mm
5SU1326-7FP06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1326-7FP06 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU1326-7FP06 is a 2-pole RCBO from the SENTRON family, combining overcurrent protection and residual current detection in a single 36 mm wide module. It carries a C-curve trip characteristic and is rated 6 A at 30 °C, with a breaking capacity of 6 kA per EN 60898 and 7.5 kA per IEC 60947-2. The 6 kA per EN 60898 covers domestic/commercial fault levels; the 7.5 kA per IEC 60947-2 gives headroom for industrial panel coordination.

Temperature derating — the real-world current rating

Like all thermal-magnetic RCBOs, the 5SU1326-7FP06 derates with ambient temperature. At 30 °C it carries 6 A; at 40 °C it drops to 5.7 A; at 50 °C to 5.3 A; at 60 °C to 5 A; and at 70 °C to 4.7 A. If the panel runs hot — near a drive cabinet or in a sealed enclosure — size up or account for the reduced capacity. IP20 applies only when installed in the enclosure.

Frequently asked questions

Will 5SU1326-7FP06 drop into a panel specified around 5SY7210-7CC without rewiring?

Both are 2-pole, 36 mm wide DIN-rail modules with top/bottom feed, so the physical fit is the same. The 5SU1326-7FP06 is an RCBO (overcurrent + residual current), while the 5SY7210-7CC is an MCB only — verify whether the circuit needs residual current protection before substituting.

MPN