Siemens 5SU1326-7FP32 SENTRON RCBO, 2-pole 32A C-curve 30mA

MPN5SU1326-7FP32
Active

Siemens SENTRON 5SU1326-7FP32 RCBO, 2-pole, 32 A rated, C tripping characteristic, 30 mA residual current Type A, breaking capacity 6 kA (EN 60898) / 7.5 kA (IEC 60947-2), IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SU1326-7FP32 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1326-7FP32 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1326-7FP32 — Mechanical
ParameterValue
Mounting positionAny
Width in modular units2
Maximum70 °C
Minimum-40 °C
Width36 mm
Height85 mm
Depth72 mm
Installation depth70 mm
5SU1326-7FP32 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1326-7FP32 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU1326-7FP32 is a 2-pole RCBO from the SENTRON series, combining overcurrent protection and residual current detection in a single 36 mm-wide module (2 modular width units). Breaking capacity is 6 kA per EN 60898 and 7.5 kA per IEC 60947-2, giving headroom for most commercial and light industrial distribution boards.

Current derating and temperature range

Above that, the unit derates linearly: 30.8 A at 40 °C, 30.2 A at 45 °C, 29.5 A at 50 °C, 29.2 A at 55 °C, and 28.8 A at 60 °C. If the distribution board runs warm — say, a packed enclosure near a heat source — factor the 40 °C or 50 °C column into the load calculation.

Snap-on mounting to DIN rail, any position. Supply can enter from top or bottom — no orientation constraint. Touch protection is built in (finger-safe terminals with connected conductors). IP20 rated, meaning it is protected against solid objects over 12 mm but not against moisture — keep it inside a closed panel or enclosure.

Frequently asked questions

Where can I buy 5SU1326-7FP32 and how do I get a price?

This RCBO is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability; the quote will reflect real-time supply.

What is the difference between 5SU1326-7FP32 and the 5SL6550-7BB?

The 5SL6550-7BB is a different class of device — a miniature circuit breaker (MCB), not an RCBO. It lacks the integrated residual current protection (30 mA Type A) that the 5SU1326-7FP32 provides. If the circuit requires combined overcurrent and earth-fault protection in one module, the 5SU1326-7FP32 is the correct fit; a separate RCCB would be needed alongside the 5SL6550-7BB.

What is the depth of 5SU1326-7FP32?

Overall depth is 72 mm; installation depth (behind the panel face) is 70 mm.

What is the width of 5SU1326-7FP32?

Width is 36 mm, which corresponds to 2 modular width units on a standard DIN-rail distribution board.

Will 5SU1326-7FP32 drop into a panel specified around 5SL6550-7BB without rewiring?

Not directly. The 5SL6550-7BB is a 2-pole MCB with no residual current module. The 5SU1326-7FP32 is an RCBO that includes the RCD function, so the wiring must accommodate the additional neutral connection for the electronic trip circuit. Physically, both are 2-module-width (36 mm) DIN-rail devices, so the footprint matches, but the circuit design differs.

What compliance documentation does Siemens provide for 5SU1326-7FP32?

The product carries IEC 60898 and IEC 60947-2 ratings, which implies CE marking for the European market. RoHS and REACH compliance are standard for current SENTRON production, but specific declarations should be requested with the RFQ.