Thermal derating and ambient limits
Above that, the continuous current must be derated: 9.6 A at 40 °C, 9.4 A at 45 °C, 9.1 A at 50 °C, 8.9 A at 55 °C, and 8.6 A at 60 °C.
Residual current and protection characteristics
Type A residual current detection means it catches sinusoidal AC faults and pulsating DC faults up to 30 mA — the standard for circuits with single-phase electronics, switched-mode power supplies, or rectifier loads. All three poles are protected (3P design), and the supply can enter from top or bottom — no orientation constraint during wiring.