Skip to main content
Siemens 5SU1336-7FP32 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1336-7FP32 SENTRON RCBO, 32 A, 6 kA, Type C, 3P

MPN5SU1336-7FP32
Active

Siemens SENTRON RCBO, 5SU1336-7FP32, 3-pole, 32 A (30 °C), C-curve, 6 kA per EN 60898, 400 V AC, 50 Hz, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1336-7FP32 — Electrical Ratings
ParameterValue
Number of poles3
Overvoltage categoryIII
5SU1336-7FP32 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1336-7FP32 — Mechanical
ParameterValue
Mounting positionany
Width in modular units3
Maximum70 °C
Minimum-40 °C
Width54 mm
Height85 mm
Depth72 mm
Installation depth70 mm
5SU1336-7FP32 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1336-7FP32 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The 5SU1336-7FP32: The 32 A rating at 30 °C is the headline figure, but the derating curve matters more for a warm enclosure: at 40 °C it carries 30.8 A, at 50 °C it drops to 29.5 A, and at 70 °C it is down to 26.9 A. If your panel ambient runs at 50 °C, size the load to 29.5 A continuous, not 32 A. For purely resistive loads with no inrush, a B-curve would be a tighter fit; for high-inrush transformers, a D-curve would be needed. Breaking capacity of 6 kA per both EN 60898 and IEC 60947-2 means it safely interrupts a 6 kA prospective fault current at 400 V AC — sufficient for most commercial and light industrial distribution boards fed by a transformer of typical impedance. The 500 V insulation voltage (Ui) and overvoltage category III confirm it is rated for fixed-installation mains distribution, not just final circuits.

Depth is 72 mm, installation depth 70 mm — fits standard 80 mm deep enclosures. Mounting position is any, so horizontal or vertical orientation is fine as long as the distribution board is IP20 rated with conductors connected.

Frequently asked questions

What is the breaking capacity of the 5SU1336-7FP32?

It is rated 6 kA per both EN 60898 and IEC 60947-2 at 400 V AC, with a 4 kV surge voltage resistance.

What is the temperature derating for this RCBO?

At 30 °C it is rated 32 A; at 40 °C it derates to 30.8 A, at 50 °C to 29.5 A, at 60 °C to 28.2 A, and at 70 °C to 26.9 A.

Where can I buy the 5SU1336-7FP32?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What compliance documentation is available for the 5SU1336-7FP32?

The part carries EN 60898 and IEC 60947-2 ratings. Specific RoHS, REACH, and UL documentation should be confirmed at quote time against the manufacturer's current declarations.

MPN
5SU1336-7FP32