Rated 25 A at 30 °C and 400 V AC, 50 Hz, with a 6 kA breaking capacity per EN 60898 and IEC 60947-2.
Rated current is temperature-dependent: 25 A at 30 °C, derating to 24 A at 40 °C, 23.5 A at 45 °C, 23 A at 50 °C, 22.5 A at 55 °C, 22 A at 60 °C, and 21 A at 70 °C. In a warm panel (40–50 °C ambient), expect to size the circuit at 23–24 A continuous load.