Siemens SENTRON 5SU1346-7FP32 — RCBO for final-distribution protection
It combines a 32 A thermal-magnetic overcurrent trip (C-curve) with residual-current detection in one unit, saving a DIN-rail slot compared to separate MCB+RCCB pairs. Rated 32 A at 30 °C ambient, it derates to 26.9 A at 70 °C — a thermal curve worth checking if the RCBO sits in a crowded, warm enclosure. The C-curve characteristic (5–10× In magnetic trip) suits mixed resistive and moderate motor-starting loads common in commercial and light-industrial final circuits.
Depth is 72 mm, height 85 mm — fits standard distribution boards with 70 mm installation depth allowance. Surge current withstand is 0.25 kA.