Skip to main content
Siemens 5SU1353-1KK16 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1353-1KK16 SENTRON RCBO, 16 A C-curve, 1P+N

MPN5SU1353-1KK16

Siemens SENTRON 5SU1353-1KK16, RCBO, 1P+N, C-curve 16 A, 4.5 kA (EN 60898) / 15 kA (IEC 60947-2), 2 MW, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SU1353-1KK16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1353-1KK16 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1353-1KK16 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1353-1KK16 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1353-1KK16 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

RCBO, C-curve, 16 A — panel fit and protection coordination

Breaking capacity is rated 4.5 kA per EN 60898 (the domestic-standard curve) and 15 kA per IEC 60947-2 (the industrial-standard). At 4.5 kA it also covers the residential final-circuit requirement. Supply cord can enter from top or bottom — no forced busbar orientation on this design. Mounting position is any, so vertical or horizontal panel layouts work equally.

Temperature derating — real-world current capacity

At 40 °C it derates to 15.2 A; at 50 °C to 14.4 A; at 60 °C to 13.6 A; and at 70 °C to 12.32 A.

DIN-rail footprint and mounting

Two modular-width units (36 mm wide) on standard DIN rail. Depth is 77 mm, installation depth 70 mm. Height 90 mm. The 1P+N construction means the neutral pole is switched internally — no separate neutral bar needed downstream, which saves a terminal position in the distribution board. IP20 rating applies when installed in a distribution board with connected conductors. That's normal for enclosed panels; no special washdown or outdoor sealing on this unit.

Frequently asked questions

Where can I buy 5SU1353-1KK16 and how do I get a price?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 5SU1353-1KK16?

4.5 kA per EN 60898 and 15 kA per IEC 60947-2. The 15 kA figure is the industrial-standard rating for panel coordination.

What is the temperature derating for 5SU1353-1KK16?

Rated 16 A at 30 °C, derating to 15.2 A at 40 °C, 14.4 A at 50 °C, 13.6 A at 60 °C, and 12.32 A at 70 °C.

Will 5SU1353-1KK16 drop into a panel specified around 5SU9354-7KK16 without rewiring?

Both are 2-MW DIN-rail RCBOs, but the 5SU9354-7KK16 is a B-curve device, while this is C-curve. The footprint and pole configuration may differ — verify the neutral switching arrangement and the busbar pitch before swapping

MPN