Siemens 5SU1353-1KK25 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SU1353-1KK25 RCBO, 25A C-curve, 1P+N, 4.5kA

MPN5SU1353-1KK25

Siemens SENTRON series, RCBO, order code 5SU1353-1KK25, 25 A rated at 30 °C, C-curve trip characteristic, 1P+N, 4.5 kA per EN 60898, 15 kA per IEC 60947-2.

$30.48Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SU1353-1KK25 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1353-1KK25 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1353-1KK25 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1353-1KK25 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1353-1KK25 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

It protects a single-phase final subcircuit (1P+N, neutral switched) against overload, short-circuit, and earth leakage. The C-curve trip characteristic means it holds 5–10× rated current momentarily, so it's the standard choice for motor-starter and general-purpose loads that draw a moderate inrush without nuisance tripping.

Thermal derating matters here

At 40 °C it derates to 23.5 A, at 50 °C to 21.75 A, and at 70 °C to 18.25 A.

Breaking capacity — two standards, two numbers

Rated short-circuit breaking capacity is 4.5 kA per EN 60898 (the household-standard test) and 15 kA per IEC 60947-2 (the industrial-standard test). The higher IEC figure applies when the device is installed in an industrial distribution board with a higher prospective fault current — that's the number the panel designer needs for the SCCR label.

Integration notes

Two modular-width units (36 mm) snap onto standard DIN rail. Depth is 77 mm, installation depth 70 mm — check gland-plate clearance before wiring. IP20 rating applies only with the distribution board closed and conductors connected; open-door work requires a lockout.

Frequently asked questions

Where can I buy 5SU1353-1KK25 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a quote request; availability and current pricing are confirmed at quote time.

Will 5SU1353-1KK25 drop into a panel that was specified around 5SU9354-7KK16 without rewiring?

Both are 2-module-wide SENTRON RCBOs with the same DIN-rail footprint and 1P+N pole configuration, so mechanical fit is identical. The key difference is the current rating: 5SU1353-1KK25 is 25 A (C-curve), while 5SU9354-7KK16 is a different rating — verify the load before swapping.

What compliance documentation does this brand provide for 5SU1353-1KK25?

The part is halogen-free and silicon-free. It carries ratings per EN 60898 and IEC 60947-2, and is designed for overvoltage category III, pollution degree 2. Specific RoHS/REACH/UL declarations are available from the manufacturer on request.