Siemens 5SU1353-1KL40 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1353-1KL40 SENTRON RCBO, 40 A, Type C, 4.5 kA

MPN5SU1353-1KL40

Siemens SENTRON RCBO, 5SU1353-1KL40, 1P+N, 40 A at 30 °C, Type C, 4.5 kA (EN 60898) / 5 kA (IEC 60947-2), 2 MW, IP20, 77×36×90 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SU1353-1KL40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1353-1KL40 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1353-1KL40 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1353-1KL40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1353-1KL40 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU1353-1KL40 is a SENTRON-series residual current circuit breaker with overcurrent protection (RCBO) in a 1P+N, 2-pole format, combining ground-fault and short-circuit/overload protection in one 36 mm wide (2 MW) module. Breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 — enough for most sub-distribution boards downstream of a main breaker; the higher IEC figure covers industrial panel duty where the prospective fault current is known to be under 5 kA.

The 40 A rating holds only at 30 °C; at 40 °C it derates to 37.6 A, at 50 °C to 34.8 A, and at 70 °C to 29.2 A. Mounting position is any orientation (vertical, horizontal, flat), and supply can enter from top or bottom — useful when retrofitting into an existing board where the busbar layout is fixed.

Physical fit and compliance

Dimensions: 77 mm deep (70 mm installation depth behind the panel face), 36 mm wide (2 modular width units), 90 mm tall. Fits standard DIN-rail enclosures with 2-pole busbar takeoffs. Overvoltage category III, pollution degree 2, surge voltage resistance 4 kV — suitable for fixed-installation distribution boards. Halogen-free and silicon-free construction, energy limitation class 3.

Frequently asked questions

What is the rated current of 5SU1353-1KL40 and how does temperature affect it?

Rated 40 A at 30 °C ambient. It derates to 37.6 A at 40 °C, 34.8 A at 50 °C, and 29.2 A at 70 °C — size the upstream protection for the derated figure if the panel runs hot.

Where can I buy 5SU1353-1KL40 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.