Skip to main content
Siemens 5SU1353-1WM10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1353-1WM10 SENTRON RCBO, 10A C-Curve, 30mA, 1P+N

MPN5SU1353-1WM10

Siemens SENTRON 5SU1353-1WM10 RCBO, 2-pole (1P+N), 10 A rated, C-curve, 30 mA AC fault current, 4.5 kA (EN 60898), 15 kA (IEC 60947-2), 70 mm depth, 2 width units.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1353-1WM10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1353-1WM10 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SU1353-1WM10 — Mechanical
ParameterValue
Mounting positionany
Maximum75 °C
Minimum-40 °C
Installation depth70 mm

Environmental

5SU1353-1WM10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1353-1WM10 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

What this RCBO is and what it does

The Siemens 5SU1353-1WM10 is a SENTRON RCBO — a combined residual-current device and miniature circuit breaker in one 2-module-wide unit. It protects a single-phase final subcircuit against both overload/short-circuit (10 A, C-curve) and earth leakage (30 mA, type AC). The C-curve trips between 5 and 10 times rated current, so it handles moderate inrush from small motors or capacitive loads without nuisance trips. The 30 mA residual-current element catches line-to-ground faults that could cause electric shock or fire. Rated 4.5 kA breaking capacity per EN 60898, with a higher 15 kA rating per IEC 60947-2 for industrial coordination. The 1P+N configuration switches the phase and disconnects the neutral, so the neutral is opened when the device trips — important for isolating the circuit completely. It accepts supply from either top or bottom, which simplifies panel wiring. Touch protection is built in, and the housing is halogen-free and silicon-free, meeting clean-environment requirements for semiconductor or medical-adjacent installations.

Mounting and panel fit

Snaps onto standard 35 mm DIN rail. Installation depth is 70 mm, and it occupies 2 width units (36 mm). Mounting position is any — horizontal, vertical, or flat — so it fits tight enclosures. The IP20 rating applies only when the distribution board is installed and conductors are connected; it's not a standalone outdoor device. Overvoltage category III and pollution degree 2 suit it for fixed installations in building or industrial distribution boards. Mechanical service life is 10 000 switching cycles typical. The device withstands surge currents up to 1 kA (8/20 μs waveform), which covers most indirect lightning or switching transients in a building installation. Ambient temperature range is -40 °C to 75 °C, with max 95% humidity — wide enough for unheated plant rooms or outdoor enclosures in temperate climates.

Frequently asked questions

Where can I buy 5SU1353-1WM10 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is 5SU1353-1WM10's listed maximum temperature?

The maximum ambient temperature is 75 °C, with a minimum of -40 °C and max 95% humidity.

What compliance documentation does this brand provide for 5SU1353-1WM10?

The part is halogen-free and silicon-free. It is designed to EN 60898 and IEC 60947-2. The SENTRON series typically carries CE, UKCA, and EAC marking; specific certification documentation is available on request.

MPN
5SU1353-1WM10