Skip to main content
Siemens 5SU1353-6KV06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1353-6KV06 FI/LS RCBO Type A, 6A, 30mA, 4.5kA

MPN5SU1353-6KV06

Siemens 5SU1353-6KV06 FI/LS-protector Type A (PSE/SSF), D=70mm, IΔN 30mA, 4.5kA, 1+N-pole, B-curve 6A.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

The Siemens 5SU1353-6KV06 is a combined residual current device and miniature circuit breaker — an RCBO — in a single 1+N-pole module. It carries a B-curve 6A overcurrent trip and a 30 mA Type A residual current detection, rated for a 4.5 kA short-circuit breaking capacity. The Type A designation means it detects pulsating DC fault currents as well as sinusoidal AC, which covers modern electronic loads like switched-mode power supplies and variable-speed drives that can produce smooth DC leakage.

What the ratings mean for fit

The 6A B-curve overcurrent characteristic trips between 3 and 5 times rated current (18–30 A), suited for protecting final circuits supplying lighting, socket outlets, or small control loads. The 30 mA residual sensitivity provides personal protection against direct contact, while the Type A form catches the rectified fault currents that a standard AC-only RCD would miss. The 4.5 kA breaking capacity is adequate for domestic and light commercial distribution boards where the prospective short-circuit current at the point of installation is known to be below that level.

Panel integration

The 70 mm depth (D=70mm) fits standard DIN-rail enclosures and distribution boards without protruding past the cover. The 1+N-pole format occupies a single module width on the rail, with the switched neutral integrated into the same housing — no separate neutral bar connection needed downstream of the device.

Frequently asked questions

What does Type A mean on this RCBO?

Type A residual current detection means the device trips on sinusoidal AC faults and also on pulsating DC fault currents up to 6 mA smooth DC superimposed — the type of leakage common from rectifier circuits in electronics, LED drivers, and VFDs. A standard Type AC RCD would not reliably detect those pulsating DC faults.

How do I get pricing and availability for 5SU1353-6KV06?

The part is sourced to order against an RFQ through independent distribution. Submit a request with your target quantity and delivery window; availability and current pricing are confirmed at quote time.

MPN