Siemens 5SU1353-7KK10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1353-7KK10 SENTRON RCBO, 10 A, C-curve, 4.5 kA

MPN5SU1353-7KK10

Siemens SENTRON RCBO, 5SU1353-7KK10, 1P+N, 10 A at 30 °C, C-curve, 4.5 kA (EN 60898) / 15 kA (IEC 60947-2), 2 MW, IP20, halogen-free.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1353-7KK10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1353-7KK10 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1353-7KK10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1353-7KK10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1353-7KK10 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

It protects a single-phase final subcircuit against overload, short-circuit, and earth leakage. Breaking capacity is 4.5 kA per EN 60898 and 15 kA per IEC 60947-2, so it clears faults up to those levels without welding contacts.

At 10 A, that's 50 to 100 A instantaneous trip. The unit is 1P+N (switched phase, switched neutral), so it disconnects both conductors on fault. Rated insulation voltage is 264 V, surge voltage resistance 4 kV, overvoltage category III — suitable for fixed-installation distribution boards. Operating frequency is 50 Hz only. Temperature derating is published: at 40 °C the rating drops to 9.5 A, at 50 °C to 9 A, at 60 °C to 8.5 A.

Width is 2 modular units (36 mm), depth 77 mm, installation depth 70 mm. Mounting position any — no derating for upside-down or horizontal. Supply can enter from top or bottom. IP20 with conductors connected and distribution board installed. Pollution degree 2, so it's fine for normal dry indoor environments.

Frequently asked questions

What is 5SU1353-7KK10's listed depth?

Depth is 77 mm, installation depth 70 mm.

What is 5SU1353-7KK10's listed width?

Width is 36 mm, which is 2 modular units on a DIN rail.

Will 5SU1353-7KK10 drop into a panel specified around 5SU9354-7KK16 without rewiring?

Both are 2-MW SENTRON RCBOs with the same DIN-rail footprint and 1P+N topology, so mechanical fit is identical. However, the 5SU9354-7KK16 has a different current rating and tripping characteristic — verify the circuit's load and selectivity requirements before swapping.

MPN
5SU1353-7KK10