Skip to main content
Siemens 5SU1353-7KK13 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1353-7KK13 SENTRON RCBO, 2-pole 13A C-curve 30mA

MPN5SU1353-7KK13

Siemens SENTRON 5SU1353-7KK13 RCBO, 2-pole (1P+N), 13 A rated current, C tripping characteristic, 30 mA Type A residual current, 4.5 kA / 15 kA breaking capacity.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1353-7KK13 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1353-7KK13 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SU1353-7KK13 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1353-7KK13 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1353-7KK13 — Electrical
ParameterValue
Tripping Characteristic ClassC
Operational current / at AC / rated value13 A

Product details

What this RCBO is and what it does

The Siemens 5SU1353-7KK13 is a SENTRON RCBO — a combined residual-current device and miniature circuit breaker in a single 2-module-wide (36 mm) package. It occupies one pole plus neutral (1P+N) and switches the neutral conductor. Rated at 13 A with a C tripping curve, it handles moderate inrush from motorized or capacitive loads while providing 30 mA Type A residual-current protection for sinusoidal AC and pulsating DC fault currents. Breaking capacity is rated at 4.5 kA per EN 60898 for domestic-style installation and 15 kA per IEC 60947-2 for industrial distribution boards. The higher IEC figure gives the panel designer headroom for fault-current coordination downstream of a larger upstream breaker. This is a current-production part. Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

DIN-rail footprint and panel integration

At 36 mm wide (2 modular units), 90 mm tall, and 77 mm deep, the 5SU1353-7KK13 snaps onto standard DIN rail and requires 70 mm installation depth behind the panel surface. Mounting position is unrestricted. Supply can enter from either top or bottom, which simplifies bus-bar routing in crowded enclosures. IP20 rating applies once installed in a distribution board with connected conductors. Overvoltage category III and pollution degree 2 suit fixed-installation environments.

Construction and environmental range

Halogen-free and silicon-free construction — relevant for clean-room or semiconductor-adjacent panels where outgassing or silicone contamination is a concern. Ambient operating range spans -40 °C to 75 °C, with max 95% humidity.

Frequently asked questions

What is the breaking capacity of 5SU1353-7KK13?

4.5 kA per EN 60898 and 15 kA per IEC 60947-2.

What does the C-curve and 30 mA Type A mean for this RCBO?

C-curve trips at 5–10× rated current (13 A), so it tolerates motor and capacitor inrush without nuisance tripping. Type A residual detection covers sinusoidal AC and pulsating DC fault currents up to 30 mA, which is the standard threshold for personnel protection.

Where can I buy 5SU1353-7KK13 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
5SU1353-7KK13