It protects a single-phase 230/240 V AC circuit at 50 Hz, with a B-curve overcurrent trip for lighting or general-purpose loads and a Type AC residual-current trip for sinusoidal AC faults. The unit is rated 20 A at 30 °C and carries a 10 kA breaking capacity per EN 60898 (20 kA per IEC 60947-2), so it handles typical domestic or light commercial fault levels without upstream coordination worries.
Fit and derating
At 36 mm wide and 77 mm deep (70 mm installation depth), this RCBO drops into a standard DIN-rail distribution board with IP20 protection once installed and conductors connected. The temperature derating is published: 20 A at 30 °C, 18.8 A at 40 °C, 16.2 A at 55 °C, down to 14.6 A at 70 °C — so if your panel runs hot, size the circuit accordingly.