Siemens 5SU1354-0KK40 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-0KK40 SENTRON RCBO, 40 A, B Curve, 10 kA

MPN5SU1354-0KK40

Siemens SENTRON 5SU1354-0KK40 RCBO, 2-pole, 40 A rated, B characteristic, 10 kA (EN 60898), type AC residual current, 2 modular width units.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1354-0KK40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1354-0KK40 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SU1354-0KK40 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1354-0KK40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1354-0KK40 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

RCBO for 50 Hz distribution boards

The Siemens 5SU1354-0KK40 is a 2-pole residual current operated circuit breaker (RCBO) from the SENTRON series, combining overcurrent protection and residual current detection in a single 36 mm wide (2 modular width units) package for 50 Hz systems. Rated at 40 A with a B tripping characteristic. Energy limitation class 3. The residual current element is type AC, meaning it detects sinusoidal AC fault currents only — suited for circuits without rectified or pulsed DC loads.

Breaking capacity and selectivity

Short-circuit breaking capacity is rated at 10 kA per EN 60898 and 15 kA per IEC 60947-2. The higher IEC figure applies when the device is used as an industrial molded-case equivalent; the EN figure governs residential and commercial distribution board coordination. Energy limitation class 3 means the let-through energy is low enough to protect downstream wiring and loads under fault conditions — relevant for selectivity studies with upstream SENTRON NH fuse-links or SENTRON 3VA breakers.

Thermal derating and installation constraints

Full 40 A rating holds at 30 °C ambient. Derate to 37.6 A at 40 °C, 36.4 A at 45 °C, 34.8 A at 50 °C, 32.4 A at 55 °C and 60 °C, 30.8 A at 65 °C, and 29.2 A at 70 °C. Panel builders must apply these values when grouping multiple RCBOs in a confined enclosure. Mounting position is unrestricted, and the supply can enter from either top or bottom — simplifies busbar routing in a crowded distribution board. Installation depth is 70 mm, overall depth 77 mm. Degree of pollution 2 and overvoltage category III suit fixed-installation distribution boards. IP20 applies once the board is closed with conductors connected.

Frequently asked questions

What is the depth of 5SU1354-0KK40?

Overall depth is 77 mm; installation depth is 70 mm.