Siemens 5SU1354-0LB40 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-0LB40 SENTRON RCBO, 40 A, B Curve, 10 kA

MPN5SU1354-0LB40

Siemens SENTRON 5SU1 RCBO, 40 A, B-curve, 10 kA per EN 60898, 2-pole 1P+N, 36 mm wide.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1354-0LB40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1354-0LB40 — Identification
ParameterValue
Product designationRCBO

Mechanical

5SU1354-0LB40 — Mechanical
ParameterValue
Mounting positionany
Maximum15.6 W
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1354-0LB40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1354-0LB40 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

What it is and where it lands

The Siemens 5SU1354-0LB40 is a SENTRON RCBO — a combined residual-current circuit breaker with overcurrent protection — rated 40 A at 30 °C with a B tripping characteristic and a 10 kA breaking capacity per EN 60898. It protects a 1P+N (230 V AC) final subcircuit against overload, short-circuit, and earth leakage (AC type fault current). Two width units (36 mm) on a DIN rail; install in any mounting position, feed from top or bottom.

Current derating — the number that matters for the panel

The 40 A rating holds at 30 °C ambient. At 40 °C it's 37.6 A; at 50 °C it's 34.8 A; at 55 °C it's 32.4 A. If the panel ambient runs warm — say 45 °C inside the enclosure — the usable current drops to 36.4 A. That derating curve is the spec to check against the actual load, not the nameplate 40 A.

Panel fit and wiring

The RCBO is 36 mm wide (2 width units), 90 mm tall, 77 mm deep with an installation depth of 70 mm. Terminals accept solid or stranded conductors from 0.75 mm² up to 35 mm². Halogen-free and silicon-free construction. IP20 with the distribution board installed and conductors connected. Overvoltage category III, energy limiting class 3.

Frequently asked questions

Is 5SU1354-0LB40 available via RFQ confirmation and what is the lead time?

The part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 5SU1354-0LB40's listed depth?

The depth is 77 mm, with an installation depth of 70 mm.

What conductor sizes does 5SU1354-0LB40 accept?

Solid and stranded conductors from 0.75 mm² up to 35 mm².

What compliance documentation does this brand provide for 5SU1354-0LB40?

The product is designed to EN 60898 (10 kA breaking capacity) and carries overvoltage category III classification. It is halogen-free and silicon-free. Specific RoHS/REACH/UL declarations should be confirmed at quote time.

MPN
5SU1354-0LB40