Siemens 5SU1354-1KK13 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-1KK13 SENTRON RCBO, 13 A, 30 mA, Type C, 1P+

MPN5SU1354-1KK13

Siemens SENTRON RCBO, 1P+N, 13 A, 30 mA, Type C, 10/20 kA, 230/240 V AC, 50 Hz, 2 MW.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1354-1KK13 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1354-1KK13 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1354-1KK13 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1354-1KK13 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1354-1KK13 — Electrical
ParameterValue
Tripping Characteristic ClassC
Operational current / at AC / rated value13 A

Product details

Siemens 5SU1354-1KK13 — SENTRON RCBO, 13 A, 30 mA, Type C

The neutral pole is switched, and the supply can enter from either the top or bottom. This is a current-production part, actively quoted through independent distribution channels.

The 30 mA residual sensitivity provides additional protection against electric shock for socket-outlet circuits and final subcircuits in residential and commercial installations. The 10 kA (EN 60898) / 20 kA (IEC 60947-2) prospective fault current ratings tell you the device can safely interrupt a short-circuit up to those levels — the higher IEC 60947-2 figure is the one that matters for industrial panel coordination. The 1P+N configuration switches both phase and neutral, with the neutral pole making and breaking; this is standard for single-phase final circuits where isolation of both conductors is required.

At 2 modular width units (36 mm wide, 90 mm tall, 77 mm deep including terminals), the 5SU1354-1KK13 snaps onto a standard DIN rail and occupies two adjacent 18 mm slots in a distribution board. The installation depth is 70 mm. Mounting position is unrestricted, and the supply cable can enter from either top or bottom. The IP20 rating is typical for enclosed distribution boards — the touch protection feature is active once conductors are connected.

Frequently asked questions

What is the rated current and residual sensitivity of 5SU1354-1KK13?

It is rated 13 A with a 30 mA residual-current trip, Type C characteristic, for 230/240 V AC, 50 Hz single-phase circuits.

What breaking capacity does 5SU1354-1KK13 have?

The breaking capacity is 10 kA per EN 60898 and 20 kA per IEC 60947-2, covering standard distribution-board fault levels.

What is the physical size of 5SU1354-1KK13?

It is 36 mm wide (2 modular units), 90 mm tall, and 77 mm deep, with an installation depth of 70 mm. It snaps onto a standard DIN rail.

Where can I buy 5SU1354-1KK13 and how is it quoted?

The part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN