Skip to main content
Siemens 5SU1354-1LB10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-1LB10 SENTRON RCBO, 10 A C-curve, 2-pole 1P+

MPN5SU1354-1LB10

Siemens SENTRON 5SU1354-1LB10 RCBO, 2-module width, 10 A rated, C tripping characteristic, AC residual current type, 10 kA (EN 60898) / 20 kA (IEC 60947-2) breaking capacity.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1354-1LB10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1354-1LB10 — Identification
ParameterValue
Product designationRCBO
Product design / constructionShort-time delayed G, super resistant K

Mechanical

5SU1354-1LB10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1354-1LB10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1354-1LB10 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SU1354-1LB10 is a combined residual current circuit breaker with integral overcurrent protection — an RCBO — in a 2-module-wide (36 mm) package that snaps onto standard DIN rail. It carries a 10 A rated current at 30 °C with a C tripping characteristic (magnetic release between 5× and 10× In), and its residual-current element is type AC, meaning it detects sinusoidal AC fault currents only. The unit is 1P+N, switching the line conductor while the neutral is switched through but not protected against overcurrent. Breaking capacity is rated at 10 kA per EN 60898 and 20 kA per IEC 60947-2, which gives the 5SU1354-1LB10 headroom for installation at the origin of a sub-distribution board where fault currents can exceed the lower standard. The design is listed as short-time delayed G and super resistant K, which means the residual-current element tolerates brief surge currents (from lightning or capacitor switching) without nuisance tripping, and the overcurrent element handles higher inrush without degrading — provided the prospective short-circuit current stays within the 20 kA IEC rating.

Thermal derating and mounting

The 10 A rating holds at 30 °C ambient. At 40 °C it derates to 9.5 A, at 50 °C to 9 A, and at 60 °C to 8.5 A. By 70 °C the continuous current is 7.7 A. This matters in a sealed enclosure or a crowded DIN rail where internal temperature rise is unavoidable — the designer must either load the circuit below the derated figure or ventilate the panel to keep ambient under 40 °C. Mounting position is unrestricted, which simplifies layout in a vertical or horizontal busbar system. The 5SU1354-1LB10 occupies 2 modular width units (36 mm) on the DIN rail, with an installation depth of 70 mm and overall depth of 77 mm. Supply can enter from top or bottom, which avoids re-routing when the RCBO replaces an existing unit in a wired panel. The IP20 rating applies only when the distribution board is installed with connected conductors — that is, it is not a standalone weatherproof device, so it belongs inside a rated enclosure.

Frequently asked questions

How do I get current pricing and availability for 5SU1354-1LB10?

The 5SU1354-1LB10 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What compliance documentation does the brand provide for 5SU1354-1LB10?

The 5SU1354-1LB10 is halogen-free and silicon-free, rated for overvoltage category III and pollution degree 2, and carries breaking capacity certifications per EN 60898 (10 kA) and IEC 60947-2 (20 kA). Standard Siemens SENTRON documentation includes CE declaration of conformity and RoHS/REACH compliance statements.

Will 5SU1354-1LB10 drop into a panel specified around 5SY7210-7CC without rewiring?

The 5SU1354-1LB10 is a 2-module (36 mm) RCBO with 1P+N switching and supply from top or bottom, so it fits the same DIN-rail footprint and wiring direction as the 5SY7210-7CC, provided the panel has neutral bar access for the switched neutral. The 5SY7210-7CC is a different class (MCB only, no residual-current element), so the functional replacement requires verifying the circuit's RCD protection requirements.

MPN
5SU1354-1LB10