Skip to main content
Siemens 5SU1354-1RC32 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-1RC32 SENTRON RCBO, 32 A, C-curve, 30 mA, 2-

MPN5SU1354-1RC32

Siemens SENTRON 5SU1354-1RC32, RCBO, 32 A, C characteristic, Type AC, 30 mA, 2-pole (1P+N), 10 kA / 15 kA breaking capacity.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1354-1RC32 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1354-1RC32 — Identification
ParameterValue
Product designationRCBO
5SU1354-1RC32 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SU1354-1RC32 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1354-1RC32 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SU1354-1RC32 is a 2-pole (1P+N) RCBO combining overcurrent protection and residual current detection in a single 36 mm wide (2-module) DIN-rail unit. The 4 kV surge voltage resistance (rated impulse withstand) and overvoltage category III rating confirm it is designed for fixed-installation distribution boards, not for plug-in portable use.

Depth is 70 mm, height 90 mm — fits standard enclosure cutouts. IP20 protection applies only when installed in a distribution board with conductors connected — treat it as a panel-internal device, not suitable for exposed or washdown locations.

Frequently asked questions

Where can I buy 5SU1354-1RC32 and how is it quoted?

It is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or prices are published here.

What is the breaking capacity of 5SU1354-1RC32?

10 kA per EN 60898 and 15 kA per IEC 60947-2, so it covers the majority of residential and light commercial panelboard fault levels without needing upstream fusing.

Will 5SU1354-1RC32 drop into a panel specified around 5SL4363-7?

No — the 5SL4363-7 is a 3-pole miniature circuit breaker (MCB) with a 54 mm width, while the 5SU1354-1RC32 is a 2-pole RCBO at 36 mm. They serve different functions (overcurrent-only vs combined RCD+MCB) and have different footprints; rewiring and a different DIN-space allocation would be required.

MPN
5SU1354-1RC32