Skip to main content
Siemens 5SU1354-1RC40 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-1RC40 SENTRON RCBO, 40A, 30mA, C-Curve

MPN5SU1354-1RC40

Siemens SENTRON 5SU1354-1RC40 RCBO, 2-pole 1P+N, 40 A rated current, 30 mA residual current Type AC, C tripping characteristic, 10 kA breaking capacity per EN 60898.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1354-1RC40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1354-1RC40 — Identification
ParameterValue
Product designationRCBO

Mechanical

5SU1354-1RC40 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm

Environmental

5SU1354-1RC40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1354-1RC40 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU1354-1RC40 is a SENTRON RCBO (residual current circuit breaker with overcurrent protection) rated 40 A with a 30 mA residual current trip of Type AC and a C tripping characteristic. This 2-pole, 1P+N device occupies 2 modular width units (36 mm) on a DIN rail and is designed for 50 Hz AC systems. It carries a 10 kA rated short-circuit capacity per EN 60898 and a 15 kA rating per IEC 60947-2, making it suitable for residential and light commercial distribution boards where both overcurrent and earth-fault protection are needed in a single unit.

What the ratings mean for fit

The 40 A rated current and C characteristic mean this RCBO is intended for circuits with moderate inrush currents — common for lighting banks, small motor loads, and general-purpose socket outlets. The C-curve trips at 5 to 10 times rated current, so it holds through the startup surge of a refrigerator compressor or a bank of fluorescent ballasts without nuisance tripping. The 30 mA residual-current sensitivity with Type AC detection means it responds to sinusoidal AC fault currents only — the standard choice for basic shock protection in residential and commercial circuits. It does not detect pulsating DC or smooth DC fault currents, so for circuits with variable-speed drives, UPS systems, or EV chargers, a Type A or Type F RCBO would be required. Breaking capacity: 10 kA per EN 60898 and 15 kA per IEC 60947-2. The EN 60898 rating governs its use in domestic-type installations; the higher IEC 60947-2 rating applies when installed in industrial distribution boards with higher prospective fault currents. Either way, it safely interrupts faults up to those levels without cascading upstream.

Mounting and integration

Snap-on DIN-rail mount, 2 MW (36 mm wide), 70 mm deep, 90 mm tall. The power supply can enter from either top or bottom, and the device can be mounted in any orientation. IP20 rating applies once the distribution board is installed with conductors connected — this is a panel-internal device, not for outdoor or washdown locations. Overvoltage category III and pollution degree 2 confirm it is rated for fixed-installation use downstream of the main distribution board, not for direct utility connection. Operating temperature range -40 °C to 75 °C covers most indoor and sheltered outdoor enclosures.

Frequently asked questions

What is the breaking capacity of 5SU1354-1RC40?

10 kA per EN 60898 and 15 kA per IEC 60947-2. The higher IEC rating applies in industrial distribution boards.

Where can I buy 5SU1354-1RC40?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 5SU1354-1RC40 fit in a panel designed for 5SY7210-7CC?

Both are 2-module (36 mm wide) DIN-rail devices with similar 70 mm installation depth, so the physical footprint is compatible. However, 5SY7210-7CC is a miniature circuit breaker (MCB) without residual current protection, while the 5SU1354-1RC40 is an RCBO combining overcurrent and earth-fault protection. They are not direct functional substitutes; the wiring and circuit protection scheme differ.

What compliance documentation is available for 5SU1354-1RC40?

The device carries ratings per EN 60898 and IEC 60947-2. Standard Siemens SENTRON documentation includes CE declaration of conformity; specific RoHS, REACH, and UL status should be confirmed from the manufacturer's current compliance documents at time of order.

MPN
5SU1354-1RC40