Skip to main content
Siemens 5SU1354-3KK16 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-3KK16 RCBO, Type F, 30 mA, 16 A, B Curve

MPN5SU1354-3KK16
Active

Siemens SENTRON 5SU1354-3KK16 RCBO, 1P+N, type F, 30 mA residual current, B characteristic, 16 A rated current, 10 kA / 20 kA breaking capacity.

$67.04Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SU1354-3KK16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1354-3KK16 — Identification
ParameterValue
Product designationRCBO
Product design / constructionSuper resistant K
5SU1354-3KK16 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1354-3KK16 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1354-3KK16 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

Type F residual protection for frequency-converter-fed circuits

The Siemens 5SU1354-3KK16 is a SENTRON RCBO combining overcurrent protection (B curve, 16 A) with Type F residual-current detection at 30 mA. Type F is specified for circuits where variable-speed drives, frequency converters, or other loads generate mixed-frequency leakage — it responds to AC, pulsating DC, and smooth DC residual currents up to 1 kHz, which a standard Type A cannot reliably detect.

The 90 mm height is standard for the SENTRON range, so it aligns with adjacent MCBs and RCCBs in the same enclosure. Supply can enter from either top or bottom, and the mounting position is unrestricted — the unit operates in any orientation.

Frequently asked questions

What is the difference between Type F and Type A RCBO?

Type F (as on this 5SU1354-3KK16) detects AC, pulsating DC, and smooth DC residual currents up to 1 kHz, covering leakage from frequency converters and variable-speed drives. Type A detects AC and pulsating DC only, without the high-frequency capability. For circuits with VFDs or other non-sinusoidal loads, Type F is the correct selection.

Can 5SU1354-3KK16 be used in three-phase systems?

It is designed for single-phase final circuits, not three-phase distribution.

MPN
5SU1354-3KK16