Skip to main content
Siemens 5SU1354-6FM16 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-6FM16 SENTRON RCBO, 16 A, 10 kA, Type A, B C

MPN5SU1354-6FM16

Siemens SENTRON 5SU1 series RCBO, 2-pole 1P+N, 16 A rated, 10 kA breaking capacity per EN 60898, Type A fault current, B tripping characteristic, instantaneous design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1354-6FM16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1354-6FM16 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SU1354-6FM16 — Mechanical
ParameterValue
Mounting positionany
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1354-6FM16 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1354-6FM16 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

What this RCBO delivers in the panel

The Siemens 5SU1354-6FM16 is a 2-pole 1P+N residual current operated circuit breaker (RCBO) from the SENTRON 5SU1 family, rated 16 A with a 10 kA breaking capacity per EN 60898. The Type A fault-current detection handles pulsating DC and AC residual currents — the standard choice for single-phase loads with electronic rectifiers (washing machines, LED drivers, VFD-fed pumps). The B curve trips between 3 and 5 times rated current, so it clears moderate inrush without nuisance tripping on resistive or lightly inductive circuits. Mounts on DIN rail, occupies 2 width units (36 mm), and accepts conductors from 0.75 to 35 mm² solid or stranded — enough for the incoming feed and through-wiring in a distribution board. Installation depth is 70 mm; overall depth is 77 mm including the front projection. Supply can enter from top or bottom, which simplifies panel layout when busbars run on either side.

Thermal derating — the real current rating changes with ambient

The 16 A rating holds at 30 °C ambient. At 40 °C it derates to 15.2 A, at 50 °C to 14.4 A, and at 60 °C to 13.6 A. By 70 °C the continuous current drops to 12.32 A. If this RCBO sits in a crowded enclosure with multiple devices dissipating heat, size the branch circuit for the derated figure at the expected internal temperature — not the 16 A nameplate.

Panel integration notes

Rated IP20 once installed in a distribution board with conductors connected — standard for enclosed panel use, not for wet or dust-exposed locations. Ambient operating range is -25 to +55 °C; storage range extends to -40 to +75 °C. Mounting position is unrestricted, so it can sit sideways or upside-down in a tight enclosure without affecting the trip performance. Overvoltage category III suits fixed-installation downstream of the utility meter.

Frequently asked questions

How do I get current pricing and availability for 5SU1354-6FM16?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the depth of 5SU1354-6FM16?

Overall depth is 77 mm; installation depth is 70 mm.

What conductor sizes does 5SU1354-6FM16 accept?

Accepts solid and stranded conductors from 0.75 to 35 mm².

Will 5SU1354-6FM16 drop into a panel specified around 5SL6563-7BB without rewiring?

Both are 2-pole RCBOs occupying 2 width units (36 mm) on DIN rail, but the 5SL6563-7BB carries different ratings and tripping characteristics — verify the branch-circuit current, fault-current type, and breaking capacity before substituting. The 5SU1354-6FM16 is Type A, B curve, 16 A, 10 kA; the peer part may differ.

What compliance documentation does Siemens provide for 5SU1354-6FM16?

The part is designed per EN 60898 (breaking capacity rated at 10 kA) and carries the DIN EN 61346-2 and DIN EN 81346-2 function designations (F). It is halogen-free and silicon-free. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration at quote time.

MPN