Skip to main content
Siemens 5SU1354-6KK06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-6KK06 SENTRON RCBO, 6A B-Curve, 10kA EN 6089

MPN5SU1354-6KK06
Active

Siemens SENTRON 5SU1354-6KK06 RCBO, 1P+N, 6 A rated at 30 °C, B tripping characteristic, 10 kA (EN 60898) / 35 kA (IEC 60947-2), 2 MW, halogen-free.

$74.41Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1354-6KK06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1354-6KK06 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1354-6KK06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1354-6KK06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1354-6KK06 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The Siemens SENTRON 5SU1354-6KK06 is a 1P+N RCBO (residual current circuit breaker with overcurrent protection) rated 6 A at 30 °C with a B tripping characteristic. It breaks fault currents up to 10 kA per EN 60898 and 35 kA per IEC 60947-2, covering the typical domestic and light commercial panel requirements.

At 40 °C it derates to 5.7 A, at 50 °C to 5.4 A, and at 70 °C to 4.62 A — so in a warm enclosure the actual continuous current capacity drops. The 10 kA breaking capacity under EN 60898 is the domestic standard; the 35 kA under IEC 60947-2 gives headroom for industrial distribution where fault levels are higher. The rated insulation voltage is 264 V and the surge voltage resistance is 4 000 V, consistent with overvoltage category III and pollution degree 2 — typical for fixed-installation switchgear.

Panel integration

The 36 mm width (2 modular units) and 77 mm depth fit standard DIN-rail enclosures; installation depth is 70 mm.

Frequently asked questions

Where can I buy 5SU1354-6KK06?

It is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 5SU1354-6KK06?

10 kA per EN 60898 and 35 kA per IEC 60947-2.

What is the rated current of 5SU1354-6KK06 and how does it derate with temperature?

Rated 6 A at 30 °C; derates to 5.7 A at 40 °C, 5.4 A at 50 °C, and 4.62 A at 70 °C.

What compliance documentation does Siemens provide for 5SU1354-6KK06?

The device is halogen-free and silicon-free, and carries ratings per EN 60898 and IEC 60947-2. Specific RoHS/REACH/UL declarations should be confirmed at quote time from the supplier.

MPN
5SU1354-6KK06