Skip to main content
Siemens 5SU1354-6LB10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-6LB10 SENTRON RCBO, 2-pole 10A Type A, 10kA

MPN5SU1354-6LB10
Active

Siemens SENTRON 5SU1354-6LB10 RCBO, 2-pole (1P+N), 10 A rated, Type A residual current, B-curve, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 2 MW, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1354-6LB10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1354-6LB10 — Identification
ParameterValue
Product designationRCBO
Product design / constructionShort-time delayed G, super resistant K
5SU1354-6LB10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1354-6LB10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1354-6LB10 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The Siemens 5SU1354-6LB10 is a SENTRON RCBO (residual current circuit breaker with overcurrent protection) combining a 2-pole (1P+N) miniature circuit breaker with a Type A residual current device in a single 2-module-width (36 mm) package. Breaking capacity is 10 kA per EN 60898 and 20 kA per IEC 60947-2, giving the part headroom for high-fault installations — the IEC 60947-2 rating is the one to use when coordinating with upstream devices in an industrial panel.

Thermal derating — the real-world current rating

Above that, derate linearly: 9.5 A at 40 °C, 9 A at 50 °C, 8.5 A at 60 °C, and 7.7 A at 70 °C. In a warm enclosure (50 °C+), the effective continuous current is closer to 9 A — factor that into the load calculation.

Snaps onto DIN rail, 2 MW wide (36 mm).

Construction and compliance

Energy limitation class 3 — meaning it limits let-through energy to a low level during a fault, protecting downstream equipment.

Frequently asked questions

What is the depth of 5SU1354-6LB10?

Overall depth is 77 mm; installation depth (behind the panel face) is 70 mm.

What is the width of 5SU1354-6LB10?

Width is 36 mm, which corresponds to 2 modular width units (MW) on a standard DIN-rail panel.

MPN
5SU1354-6LB10