Skip to main content
Siemens 5SU1354-6LB40 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SU1354-6LB40 RCBO, B-Curve 40A, 10kA, Type

MPN5SU1354-6LB40
Active

Siemens SENTRON RCBO, 5SU1354-6LB40, B-curve 40 A, 2-pole 1P+N, Type A residual current, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 2 MW units, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1354-6LB40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1354-6LB40 — Identification
ParameterValue
Product designationRCBO
Product design / constructionShort-time delayed G, super resistant K
5SU1354-6LB40 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1354-6LB40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1354-6LB40 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

Siemens SENTRON 5SU1354-6LB40 — RCBO, B-Curve 40 A, Type A

The Siemens SENTRON 5SU1354-6LB40 is a 2-pole (1P+N) residual current circuit breaker with overcurrent protection (RCBO) rated 40 A at 30 °C with a B-curve tripping characteristic. It combines a Type A residual current device (sensitive to pulsating DC and AC sinusoidal residual currents) with a thermal-magnetic overcurrent trip in a single 2-module-width (36 mm) package that snaps onto DIN rail. Breaking capacity is 10 kA per EN 60898 and 15 kA per IEC 60947-2 — the IEC 60947-2 figure is the one to use for industrial panel coordination where higher fault current is expected. The short-time delayed G characteristic and super resistant K design mean this unit tolerates brief inrush without nuisance tripping, which matters on circuits feeding small motor loads or capacitive power supplies.

At 40 °C ambient the rated current drops to 37.6 A; at 50 °C it is 34.8 A; at 70 °C it is 29.2 A. Rated IP20 with conductors connected and the distribution board installed — this is a panel-internal device, not for wet or outdoor locations.

Frequently asked questions

How do I get current pricing and availability for 5SU1354-6LB40?

Submit an RFQ through this listing. The part is sourced to order; availability and current pricing are confirmed at quote time.

What is 5SU1354-6LB40's listed depth (77 mm) on this component line?

The depth is 77 mm, with an installation depth of 70 mm. Width is 36 mm (2 modular width units), height 90 mm.

Will 5SU1354-6LB40 drop into a panel that was specified around 5SL6550-7BB without rewiring?

No — the 5SL6550-7BB is a different class (MCB, not RCBO) with different pole count and residual current functionality. The 5SU1354-6LB40 is a 1P+N RCBO with Type A residual current protection; the 5SL6550-7BB lacks the RCD element entirely. Panel wiring and neutral bar arrangement would differ.

What compliance documentation does this brand provide for 5SU1354-6LB40 (RoHS, REACH, UL, IEC)?

The device is designed to EN 60898 and IEC 60947-2 for breaking capacity, carries overvoltage category III, and pollution degree 2. Halogen-free and silicon-free construction is confirmed. For specific RoHS/REACH/UL declarations, request the manufacturer's compliance documentation at quote time.

MPN
5SU1354-6LB40