Skip to main content
Siemens 5SU1354-7LB16 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-7LB16 SENTRON RCBO, 16A C-curve, 10kA

MPN5SU1354-7LB16
Active

Siemens SENTRON 5SU1354-7LB16 RCBO, 1P+N, 16 A at 30 °C, C characteristic, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 2 MW, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1354-7LB16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1354-7LB16 — Identification
ParameterValue
Product designationRCBO
Product design / constructionShort-time delayed G, super resistant K
5SU1354-7LB16 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1354-7LB16 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1354-7LB16 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The EN figure governs domestic-type installations; the IEC figure applies when the device is used in an industrial distribution board with higher prospective fault current.

Depth is 77 mm, installation depth 70 mm — verify the gland plate clearance if retrofitting into a shallow enclosure. Supply can enter from either top or bottom. The design is short-time delayed G (residual current) and super resistant K (overcurrent) — meaning the RCD element tolerates brief surge currents without nuisance tripping, useful on circuits with electronic loads or inrush.

Thermal derating

Rated current is 16 A at 30 °C ambient. Derate linearly: 15.2 A at 40 °C, 14.88 A at 45 °C, 14.4 A at 50 °C, 13.92 A at 55 °C, 13.6 A at 60 °C, 12.96 A at 65 °C, and 12.32 A at 70 °C. If the panel internal temperature runs above 30 °C — common in a crowded enclosure — size the upstream protective device accordingly.

Frequently asked questions

How do I get current pricing and availability for 5SU1354-7LB16?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through our independent distribution network; no firm figures are published here.

What is 5SU1354-7LB16's listed depth?

Depth is 77 mm; installation depth is 70 mm. The 7 mm difference accounts for the DIN-rail clip and conductor entry.

What compliance documentation does Siemens provide for 5SU1354-7LB16?

The device is halogen-free and silicon-free. It carries an IP20 protection class and is rated for overvoltage category III, pollution degree 2. Standard Siemens declarations (CE, UKCA) apply per the SENTRON series documentation.

MPN
5SU1354-7LB16