Skip to main content
Siemens 5SU1354-7LB40 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SU1354-7LB40 RCBO, 40 A, 30 mA, Type A, C-c

MPN5SU1354-7LB40
Active

Siemens SENTRON RCBO, 2-pole, 40 A, 30 mA, Type A, C-curve, 10 kA, 2 MW, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1354-7LB40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1354-7LB40 — Identification
ParameterValue
Product designationRCBO
Product design / constructionShort-time delayed G, super resistant K

Mechanical

5SU1354-7LB40 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1354-7LB40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1354-7LB40 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SU1354-7LB40 is a 2-pole RCBO (residual current circuit breaker with overcurrent protection) rated 40 A with a 30 mA residual trip threshold. It carries a Type A residual current characteristic for AC and pulsating DC fault currents, and a C tripping curve for the overcurrent element — meaning the magnetic release trips at 5 to 10 times rated current, typical for motor and lighting circuits with moderate inrush. The breaking capacity is 10 kA per EN 60898, which certifies its ability to safely interrupt fault currents up to that level in a 50/60 Hz network.

Ratings and derating

At 30 °C ambient the device carries the full 40 A. Derate linearly: 37.6 A at 40 °C, 36.4 A at 45 °C, 34.8 A at 50 °C, 32.4 A at 55 °C and 60 °C, 30.8 A at 65 °C, and 29.2 A at 70 °C. The thermal curve is the governing spec for panel placement — if the RCBO sits next to other heat sources in a crowded enclosure, use the 40 °C or 45 °C row as the design current, not the 30 °C headline.

Mounting and integration

Two modular width units (36 mm wide) snap onto a DIN rail. The 77 mm depth and 70 mm installation depth fit standard distribution boards. Mounting position is unrestricted — any orientation works. Supply can enter from top or bottom. Touch protection is built in. The IP20 rating applies once installed in a distribution board with conductors connected; the device itself is not rated for wet or dusty environments without an enclosure.

Frequently asked questions

Where can I buy 5SU1354-7LB40 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What are the key ratings of 5SU1354-7LB40?

40 A rated current, 30 mA residual trip, Type A residual current characteristic, C tripping curve, 10 kA breaking capacity per EN 60898, 2-pole, 2 MW width, IP20.

What is the depth of 5SU1354-7LB40?

The depth is 77 mm; installation depth is 70 mm.

What compliance documentation is available for 5SU1354-7LB40?

The device is halogen-free and silicon-free. It carries an IP20 protection class, overvoltage category III, and pollution degree 2. The breaking capacity is certified per EN 60898. For specific RoHS, REACH, or UL declarations, the manufacturer's documentation is available on request.

MPN
5SU1354-7LB40