Skip to main content
Siemens 5SU1354-7RC40 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-7RC40 SENTRON RCBO, 40 A, Type A, 30 mA, C-c

MPN5SU1354-7RC40

Siemens SENTRON 5SU1354-7RC40 RCBO, 40 A, 2-pole, 2-module, C characteristic, Type A, 30 mA residual current, 10 kA (EN 60898) / 15 kA (IEC 60947-2).

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1354-7RC40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1354-7RC40 — Identification
ParameterValue
Product designationRCBO
5SU1354-7RC40 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SU1354-7RC40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1354-7RC40 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU1354-7RC40 is a SENTRON RCBO (residual current circuit breaker with overcurrent protection) rated 40 A at 50 Hz AC, combining a C-curve MCB and a Type A RCD in a single 2-module (36 mm wide) package.

The higher IEC figure applies when the RCBO is used as a circuit breaker in industrial distribution — the EN value governs residential or commercial final circuits.

Depth is 70 mm, height 90 mm. Mounting position is unrestricted — can be installed horizontally or vertically. Supply can enter from either top or bottom. The IP20 rating applies with the distribution board closed and conductors connected; the enclosure provides the environmental seal, not the device itself.

Environmental range

That covers unheated enclosures in cold climates and high-temp machine cabinets near ovens or drives.

Listed as current production (active lifecycle stage). The 5SU1354-7RC40 is a standard catalog item in the SENTRON range.

Frequently asked questions

How do I get current pricing and availability for 5SU1354-7RC40?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time against the current market; the part is sourced to order through independent distribution.

What is 5SU1354-7RC40's listed depth?

Depth is 70 mm, matching the standard 70 mm installation depth for SENTRON modular devices.

What is 5SU1354-7RC40's listed width?

Width is 36 mm, which corresponds to 2 modular width units on a DIN rail.

Will 5SU1354-7RC40 drop into a panel specified around 5SL4106-7CC without rewiring?

No — 5SL4106-7CC is a 1-pole MCB (18 mm wide), while the 5SU1354-7RC40 is a 2-pole RCBO (36 mm wide). The footprint and function are different; the panel would need rewiring and a wider slot.

MPN