Skip to main content
Siemens 5SU1354-7VK10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-7VK10 SENTRON RCBO, 2-pole, 10 A, 30 mA, Typ

MPN5SU1354-7VK10

Siemens SENTRON 5SU1354-7VK10, RCBO, 2-pole, 10 A rated, 30 mA Type A residual current, tripping characteristic C, breaking capacity 10 kA per EN 60898 / 20 kA per IEC 60947-2, 2 MW units, IP20.

$157.52Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1354-7VK10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1354-7VK10 — Identification
ParameterValue
Product designationRCBO
Product design / constructionSuper resistant K
5SU1354-7VK10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1354-7VK10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1354-7VK10 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

What this RCBO covers

The Siemens 5SU1354-7VK10 is a 2-pole RCBO from the SENTRON Super Resistant K design, combining overcurrent protection (characteristic C) and residual current protection (Type A, 30 mA) in a single 36 mm wide unit. It's rated 10 A at AC, with a breaking capacity of 10 kA per EN 60898 and 20 kA per IEC 60947-2. The 30 mA trip threshold covers the standard personnel-protection requirement for socket circuits and wet-area final subcircuits. Type A detection handles pulsating DC fault currents from rectified loads — common in modern electronics, LED drivers, and variable-speed drives.

Temperature derating and panel fit

The 10 A rating holds at 30 °C ambient; it derates to 9.5 A at 40 °C, 9.3 A at 45 °C, 9 A at 50 °C, 8.7 A at 55 °C, and 8.5 A at 60 °C.

Frequently asked questions

Where can I buy 5SU1354-7VK10 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is 5SU1354-7VK10's listed depth?

The listed depth is 77 mm, with a 70 mm installation depth required in the panel.

What is 5SU1354-7VK10's listed width?

The width is 36 mm, corresponding to 2 modular width units on a standard DIN rail.

What compliance documentation does this brand provide for 5SU1354-7VK10?

The SENTRON series carries CE marking per the Low Voltage Directive and RoHS compliance as standard. Check the nameplate for specific UL or CSA listing on the unit received.

MPN
5SU1354-7VK10