Skip to main content
Siemens 5SU1354-7VK10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-7VK10 SENTRON RCBO, 2-pole, 10 A, 30 mA, Typ

MPN5SU1354-7VK10

Siemens SENTRON 5SU1354-7VK10, RCBO, 2-pole, 10 A rated, 30 mA Type A residual current, tripping characteristic C, breaking capacity 10 kA per EN 60898 / 20 kA per IEC 60947-2, 2 MW units, IP20.

$157.52Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1354-7VK10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1354-7VK10 — Identification
ParameterValue
Product designationRCBO
Product design / constructionSuper resistant K

Mechanical

5SU1354-7VK10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1354-7VK10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1354-7VK10 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

What this RCBO covers

The Siemens 5SU1354-7VK10 is a 2-pole RCBO from the SENTRON Super Resistant K design, combining overcurrent protection (characteristic C) and residual current protection (Type A, 30 mA) in a single 36 mm wide unit. It's rated 10 A at AC, with a breaking capacity of 10 kA per EN 60898 and 20 kA per IEC 60947-2. The 30 mA trip threshold covers the standard personnel-protection requirement for socket circuits and wet-area final subcircuits. Type A detection handles pulsating DC fault currents from rectified loads — common in modern electronics, LED drivers, and variable-speed drives.

Temperature derating and panel fit

The 10 A rating holds at 30 °C ambient; it derates to 9.5 A at 40 °C, 9.3 A at 45 °C, 9 A at 50 °C, 8.7 A at 55 °C, and 8.5 A at 60 °C. In a warm enclosure — say a packed panel near a drive — that 8.5 A floor at 60 °C is the figure to size against continuous load. The device occupies 2 modular width units (36 mm) and installs in any mounting position, with a 70 mm installation depth. Supply can enter from top or bottom, which simplifies busbar routing in retrofit panels.

Frequently asked questions

Where can I buy 5SU1354-7VK10 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is 5SU1354-7VK10's listed depth?

The listed depth is 77 mm, with a 70 mm installation depth required in the panel.

What is 5SU1354-7VK10's listed width?

The width is 36 mm, corresponding to 2 modular width units on a standard DIN rail.

What compliance documentation does this brand provide for 5SU1354-7VK10?

The SENTRON series carries CE marking per the Low Voltage Directive and RoHS compliance as standard. Check the nameplate for specific UL or CSA listing on the unit received.

MPN