Skip to main content
Siemens 5SU1354-7VK16 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-7VK16 SENTRON RCBO, 2-pole, 16 A, Type A, 10

MPN5SU1354-7VK16

Siemens SENTRON 5SU1354-7VK16 RCBO, 2-pole, 16 A, Type A, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 2 MW, C characteristic, halogen-free, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1354-7VK16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1354-7VK16 — Identification
ParameterValue
Product designationRCBO
Product design / constructionSuper resistant K
5SU1354-7VK16 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1354-7VK16 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1354-7VK16 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

This is the Super resistant K design, meaning the housing and internals are built for higher ambient temperatures and aggressive atmospheres — halogen-free and silicon-free, so it won't outgas or corrode sensitive contacts in sealed enclosures.

The 16 A rating holds at 30 °C ambient, but drops to 15.2 A at 40 °C, 14.4 A at 50 °C, and 12.32 A at 70 °C. That 20 kA figure is the one to use for industrial panel SCCR calculations — it tells you the device can safely interrupt a 20 kA prospective fault current at 230/400 V without welding or exploding.

Physical fit and mounting

Width is 36 mm (2 modular units), depth 77 mm, height 90 mm, with an installation depth of 70 mm behind the panel face. The IP20 rating applies when installed in a distribution board with conductors connected; the device itself isn't rated for wet or dusty environments, so keep it inside the enclosure.

Frequently asked questions

What is the breaking capacity of 5SU1354-7VK16?

10 kA per EN 60898 and 20 kA per IEC 60947-2. Use the 20 kA figure for industrial panel SCCR calculations.

What is the thermal derating for this RCBO at elevated ambient temperatures?

Rated 16 A at 30 °C, derated to 15.2 A at 40 °C, 14.4 A at 50 °C, 13.6 A at 60 °C, and 12.32 A at 70 °C. Account for this if your panel runs hot.

Where can I buy 5SU1354-7VK16 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability — no stock or lead-time figures are published here.

MPN
5SU1354-7VK16