Siemens 5SU1356-1GV16 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1356-1GV16 SENTRON RCBO, 16 A, 30 mA, Type AC, 6

MPN5SU1356-1GV16
Active

Siemens SENTRON RCBO, 2-pole, 16 A, 30 mA, Type AC, tripping characteristic C, 6 kA (EN 60898) / 15 kA (IEC 60947-2), 2 MW, IP20, halogen-free, -40 to 75 °C.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1356-1GV16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1356-1GV16 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1356-1GV16 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1356-1GV16 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1356-1GV16 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU1356-1GV16 is a SENTRON RCBO (residual current circuit breaker with overcurrent protection) combining a 16 A rated current with a 30 mA residual-current trip in a single 2-module-wide (36 mm) package.

Full 16 A rating holds at 30 °C ambient; at 40 °C it derates to 15.2 A, at 50 °C to 14.4 A, and at 70 °C to 12.32 A. Mounting position is unrestricted, and the supply can enter from either top or bottom — no forced orientation in the panel. IP20 applies once the distribution board is installed and conductors are connected — the front face is touch-protected.

Frequently asked questions

What is the breaking capacity of 5SU1356-1GV16?

6 kA per EN 60898 and 15 kA per IEC 60947-2 — the higher figure applies when the RCBO is applied under the IEC 60947-2 standard for industrial use.

What temperature derating applies to 5SU1356-1GV16?

Full 16 A at 30 °C; derates to 15.2 A at 40 °C, 14.4 A at 50 °C, and 12.32 A at 70 °C. Ambient temperature inside the enclosure governs the actual continuous rating.

Where can I buy 5SU1356-1GV16?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.