Siemens 5SU1356-1KK06 SENTRON RCBO, 6 A, Type C, 6 kA

MPN5SU1356-1KK06

Siemens SENTRON 5SU1356-1KK06 RCBO, 1P+N, 6 A, tripping characteristic C, 6 kA (EN 60898) / 25 kA (IEC 60947-2), 230/240 V AC, 50 Hz.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1356-1KK06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1356-1KK06 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SU1356-1KK06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1356-1KK06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1356-1KK06 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

What this RCBO is and where it fits

The Siemens 5SU1356-1KK06 is a SENTRON RCBO — a combined residual-current device and miniature circuit breaker in a single 2-module (36 mm wide) package. It protects a single-phase final subcircuit against both earth leakage and overcurrent/short-circuit, with a 1P+N pole arrangement (switched neutral). Rated 6 A at 30 °C with a Type C tripping characteristic (5–10× In magnetic release), it handles moderate inrush loads like small motors, lighting banks, and control transformers on 230/240 V AC 50 Hz supplies. Breaking capacity is 6 kA per EN 60898 for domestic/commercial distribution boards, and 25 kA per IEC 60947-2 for industrial panel applications — the higher figure gives selectivity headroom downstream of a larger upstream device. Overvoltage category III and pollution degree 2 suit fixed-installation environments inside enclosed distribution boards.

Dimensions and mounting — panel fit check

The 5SU1356-1KK06 occupies 2 modular width units (36 mm wide) on a DIN rail, with a depth of 77 mm and height of 90 mm. Installation depth is 70 mm. Mounting position is any orientation. Supply can enter from either top or bottom. IP20 rating applies once installed in a distribution board with conductors connected.

Thermal derating — what 6 A means at panel ambient

The 6 A rating is at 30 °C ambient. At 40 °C it derates to 5.7 A, at 50 °C to 5.4 A, and at 60 °C to 5.1 A. If your panel runs warm — common in crowded enclosures — size the circuit for the derated figure at expected ambient, not the 30 °C headline.

Frequently asked questions

What is the breaking capacity of 5SU1356-1KK06?

6 kA per EN 60898 for standard distribution board duty, and 25 kA per IEC 60947-2 for industrial panel applications.

What compliance documentation does this brand provide for 5SU1356-1KK06?

The product is halogen-free and silicon-free. It carries ratings per EN 60898 and IEC 60947-2, overvoltage category III, pollution degree 2, and IP20 when installed. Specific RoHS/REACH/UL declarations should be requested at quote time.

Who supplies 5SU1356-1KK06 and how is it quoted for volume purchases?

Sourced to order through independent distribution. Submit an RFQ for current availability and pricing — volume quotes confirmed at quote time.

Will 5SU1356-1KK06 drop into a panel that was specified around 5SL6550-7BB without rewiring?

Both are 2-module (36 mm) DIN-rail RCBOs, so the footprint is the same. But the 5SU1356-1KK06 is a 1P+N instantaneous type with a 6 A Type C characteristic, while the 5SL6550-7BB is a different variant — check the specific ratings (current, trip curve, residual sensitivity) before swapping.