RCBO with B-curve and thermal-magnetic trip
It combines overcurrent and residual current protection in a single 2-module-wide (36 mm) device, saving panel space over separate MCB and RCCB. Rated for 230/240 V AC at 50 Hz, it carries a 6 kA breaking capacity per EN 60898 and 15 kA per IEC 60947-2, with an insulation voltage of 264 V and surge voltage resistance of 4 kV. The instantaneous design (no intentional delay) suits circuits where fast disconnection is required.
Current derating and temperature range
The rated current of 10 A applies at 30 °C. Above that, derate linearly: 9.5 A at 40 °C, 9 A at 50 °C, 8.5 A at 60 °C, and 8 A at 70 °C.
Mounts in any position, with a depth of 77 mm and installation depth of 70 mm.