Temperature derating — the real current rating
At 40 °C it's 30.4 A, at 50 °C it's 28.8 A, and at 70 °C it drops to 24.64 A. If the panel runs warm — say 50 °C inside the enclosure — the continuous load should be capped at 28.8 A. That's the figure that governs the circuit design, not the 30 °C number.
Snaps onto DIN rail, 2 MW wide (36 mm), depth 77 mm, installation depth 70 mm. IP20 with conductors connected and distribution board installed — standard for enclosed distribution.