Siemens 5SU1624-1KK82 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1624-1KK82 SENTRON RCBO, 125 A, 300 mA, 10 kA, 2P

MPN5SU1624-1KK82

Siemens SENTRON 5SU1624-1KK82 RCBO, 2-pole, 125 A at 30 °C, 300 mA residual, 10 kA breaking capacity, tripping characteristic C, AC fault current.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1624-1KK82 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1624-1KK82 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1624-1KK82 — Mechanical
ParameterValue
Mounting positionany
Installation depth70 mm
5SU1624-1KK82 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1624-1KK82 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU1624-1KK82 is a 2-pole SENTRON RCBO (residual current circuit breaker with overcurrent protection) rated for 125 A at 30 °C, with a 300 mA residual trip and a 10 kA breaking capacity per EN 60898. The C characteristic means it handles moderate inrush — typical for motor and lighting circuits in commercial or industrial distribution boards. The 300 mA residual threshold is an equipment-protection level, not personnel protection; it guards against arcing faults and leakage that could damage wiring or start a fire.

The 125 A rating at 30 °C is the headline number, but the thermal derating curve matters in a warm panel: at 40 °C it's 115.62 A, at 50 °C it's 106.25 A, and at 60 °C it drops to 96.25 A. If your enclosure runs hot, size the upstream protection accordingly — don't spec a 125 A bus if the RCBO sits in a 50 °C cabinet. The 300 mA residual trip is not a GFCI for personnel — that's 30 mA or lower. This is an equipment-protection RCBO, often used behind a main switch or as a feeder protection in a distribution board where the downstream circuits have their own 30 mA RCDs. The AC fault-current type means it detects sinusoidal AC leakage only; if your load has DC components (VFDs, UPS, rectifiers), you'd need a Type A or B device.

The IP20 rating applies only when the distribution board is installed with conductors connected — it's not a standalone outdoor device. Terminal capacity accepts 6 to 50 mm² solid or stranded copper, so it handles large feeder cables without needing a lug adapter.

Frequently asked questions

Where can I buy 5SU1624-1KK82 and get a price?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the solid and stranded conductor range for 5SU1624-1KK82?

Both solid and stranded conductors from 6 to 50 mm² are accepted at the terminals.

What compliance documentation does Siemens provide for 5SU1624-1KK82?

The device carries approvals per EN 60898 and IEC 60947-2, and is halogen-free and silicon-free. Standard RoHS/REACH declarations are available from Siemens upon request.