The 300 mA residual sensitivity makes this a good fit for circuits where a 30 mA RCD would cause nuisance tripping — think distribution sub-mains, feeder circuits to fixed equipment, or lighting banks with higher natural leakage. The AC-type detection handles sinusoidal AC fault currents; it's not listed for pulsating DC or smooth DC faults, so keep that in mind if the load includes rectifiers or VFDs downstream.
Temperature derating and installation