Skip to main content
Siemens 5SU1644-7WK82 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SU1644-7WK82 RCBO, 125A, 4P, Type A, 10kA

MPN5SU1644-7WK82
Active

Siemens SENTRON selective RCBO, 5SU1644-7WK82, 125 A rated current, 4-pole, Type A, C-curve, 10 kA breaking capacity per EN 60898 and IEC 60947-2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1644-7WK82 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SU1644-7WK82 — Identification
ParameterValue
Product designationRCBO
Product design / constructionselective
5SU1644-7WK82 — Mechanical
ParameterValue
Mounting positionany
Width198 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1644-7WK82 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1644-7WK82 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

Selectivity and derating — the numbers that decide the panel design

This is a selective (time-delayed) RCBO, energy limiting class 3. That means it rides through short-duration inrush and lets downstream MCBs trip first — essential for a distribution board feeding multiple sub-circuits where you want only the faulted branch to open. The trade-off is a wider body: 11 width units (198 mm wide, 90 mm tall, 77 mm deep, 70 mm installation depth) on the DIN rail. Mounting position is unrestricted, and the supply can land on either top or bottom terminals. Derate linearly: 115.6 A at 40 °C, 111.3 A at 45 °C, 106.3 A at 50 °C, 101.3 A at 55 °C, and 96.3 A at 60 °C. Overvoltage category III means it's rated for fixed-installation supply-side duty. Terminals accept 6 to 50 mm² solid or stranded copper, which covers the full range for a 125 A feed. Touch protection is built in; IP20 is maintained once the distribution board is installed with conductors connected.

Frequently asked questions

Where can I buy the 5SU1644-7WK82 and get a price?

The 5SU1644-7WK82 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key ratings for the 5SU1644-7WK82?

Rated 125 A at 30 °C, 4-pole, Type A RCD, C-curve MCB, 10 kA breaking capacity per EN 60898 and IEC 60947-2. Wire range 6 to 50 mm² solid or stranded. Dimensions 198 x 90 x 77 mm, 11 width units on DIN rail.

What compliance documentation does Siemens provide for the 5SU1644-7WK82?

The part carries designations per DIN EN 61346-2 and DIN EN 81346-2 (function F). It is halogen-free and silicon-free. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration at quote time.

MPN
5SU1644-7WK82