Siemens 5SU1646-6FP20 SENTRON RCBO — 4P, 20 A, Type B
It operates at 400 V AC, 50 Hz, and carries a 6 kA breaking capacity per EN 60898 and IEC 60947-2.
The 400 V AC rating across 4 poles means it can protect a three-phase plus neutral circuit, or be used in single-phase split configurations. The 50 Hz operating frequency is fixed — not suitable for 60 Hz systems without verifying the manufacturer's derating. Temperature derating is published: 20 A at 30 °C drops to 19.5 A at 40 °C, 18.9 A at 50 °C, and 17.8 A at 70 °C. If the distribution board is in a warm enclosure or adjacent to heat-generating equipment, use the 40 °C or 50 °C column for your continuous load calculation.