Skip to main content
Siemens 5SU1653-1KK32 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1653-1KK32 SENTRON RCBO, 32 A, 30 mA, Type AC, C-

MPN5SU1653-1KK32

Siemens SENTRON RCBO, 5SU1653-1KK32, 1P+N, 32 A, 30 mA, Type AC, C characteristic, 4.5 kA per EN 60898, 15 kA per IEC 60947-2, 2 MW, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SU1653-1KK32 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1653-1KK32 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1653-1KK32 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1653-1KK32 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1653-1KK32 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SU1653-1KK32 is a combined residual current device and miniature circuit breaker (RCBO) in a 2-module-wide (36 mm) housing, rated 32 A with 30 mA residual sensitivity, Type AC, C characteristic.

The 4.5 kA breaking capacity per EN 60898 covers standard domestic and commercial final circuits; the 15 kA rating per IEC 60947-2 gives headroom for industrial panel applications where higher prospective fault currents are expected. The C characteristic (5–10× In magnetic trip) suits motor and lighting loads with moderate inrush — not for pure resistive or long-cable runs where a B curve would be preferred. The 30 mA residual sensitivity (Type AC) detects sinusoidal AC earth faults only — suitable for general socket outlets and lighting circuits where no pulsed DC or smooth DC fault currents are present. For variable-speed drives or EV charging, a Type A or F device would be required.

Snap-on mounting to DIN rail, any position. Depth 77 mm, installation depth 70 mm, width 36 mm (2 MW).

Frequently asked questions

What is the breaking capacity of 5SU1653-1KK32?

It carries a dual rating: 4.5 kA per EN 60898 for standard final circuits, and 15 kA per IEC 60947-2 for industrial panel applications.

Will 5SU1653-1KK32 drop into a panel specified for 5SU9354-7KK16?

Both are 2-module-wide (36 mm) RCBOs with the same depth (77 mm) and installation depth (70 mm), so they share the same DIN-rail footprint. The key difference is breaking capacity: this unit is 4.5/15 kA, while the 5SU9354-7KK16 is rated 10 kA per both EN 60898 and IEC 60947-2. Verify the required SCCR before substitution.

Where can I buy 5SU1653-1KK32?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
5SU1653-1KK32