Siemens 5SU1653-7KK06 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SU1653-7KK06 RCBO, C-curve, 6 A, 1P+N, 4.5

MPN5SU1653-7KK06
Active

Siemens SENTRON RCBO, 1P+N, C-curve, 6 A, 4.5 kA (EN 60898) / 25 kA (IEC 60947-2), 230/240 V AC, 50 Hz, 2 MW, IP20, halogen-free.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1653-7KK06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1653-7KK06 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1653-7KK06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1653-7KK06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1653-7KK06 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SU1653-7KK06 is a 1P+N RCBO (residual current circuit breaker with overcurrent protection) in a 2-module-wide (36 mm) housing, rated 6 A with a C-curve trip characteristic. It switches the line and protects the neutral, with overcurrent detection on the line pole only. Rated 230/240 V AC at 50 Hz, it carries a 4.5 kA breaking capacity per EN 60898 and 25 kA per IEC 60947-2 — the higher figure matters when the device is used as a main or branch-circuit protector in an industrial panel where fault currents can exceed domestic levels.

Above that, derate linearly: 5.7 A at 40 °C, 5.4 A at 50 °C, 5.1 A at 60 °C, and 4.62 A at 70 °C. In a crowded enclosure with multiple breakers, the real-world continuous current may be lower than the label suggests — size the load accordingly.

Installation depth is 70 mm — the extra 7 mm accounts for the terminal screws. Mounting position is any, which helps in tight retrofit panels.

Frequently asked questions

Where can I buy 5SU1653-7KK06 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is 5SU1653-7KK06's listed depth?

The depth is 77 mm, with an installation depth of 70 mm.

What is 5SU1653-7KK06's listed width?

The width is 36 mm, which is 2 modular units.

Will 5SU1653-7KK06 drop into a panel specified around 5SL6550-7BB without rewiring?

Both are 1P+N RCBOs in 2-MW width, so the mechanical fit is the same. However, the 5SU1653-7KK06 is a C-curve 6 A device; verify that the 5SL6550-7BB's rating and curve match your circuit before swapping — the trip coordination may differ.

MPN