Skip to main content
Siemens 5SU1654-0KK13 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1654-0KK13 SENTRON RCBO, 13 A, 10 kA, Type B, 1P+

MPN5SU1654-0KK13

Siemens SENTRON 5SU1654-0KK13 RCBO, 2-pole 1P+N, 13 A rated, Type B tripping characteristic, 10 kA (EN 60898) / 20 kA (IEC 60947-2) breaking capacity, halogen-free, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1654-0KK13 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1654-0KK13 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1654-0KK13 — Mechanical
ParameterValue
Mounting positionany
Maximum25 mm²
Minimum0.75 mm²
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1654-0KK13 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1654-0KK13 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The Siemens 5SU1654-0KK13 is a SENTRON RCBO — a combined residual-current circuit breaker and miniature circuit breaker in one 2-module-wide (36 mm) package, 1P+N, designed for 230 V AC single-phase circuits. It carries a 13 A rated current with a Type B tripping characteristic, protecting against both overload and short-circuit, and integrates residual-current detection for AC fault currents. Breaking capacity is rated at 10 kA per EN 60898 and 20 kA per IEC 60947-2, meaning it can safely interrupt fault currents up to those levels — the higher IEC figure gives headroom for industrial panels where the prospective short-circuit current may exceed 10 kA.

Current derating and thermal behaviour

Rated current is 13 A at 30 °C, but the RCBO derates as ambient temperature rises: 12.48 A at 40 °C, 12.22 A at 45 °C, 11.96 A at 50 °C, 11.57 A at 55 °C, 11.31 A at 60 °C, 10.53 A at 65 °C, and 10.01 A at 70 °C. For a 13 A resistive load in a 50 °C cabinet, you're limited to about 12 A.

The 36 mm width (2 width units) matches standard modular enclosure cutouts. Touch protection is built in, so accidental contact with live terminals during maintenance is prevented when the device is properly installed.

MPN
5SU1654-0KK13