Skip to main content
Siemens 5SU1654-1KK06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1654-1KK06 SENTRON RCBO, 6A C-curve 300mA, 2-pole

MPN5SU1654-1KK06

Siemens SENTRON RCBO, 2-pole, 6 A rated, C-curve, 300 mA residual current, 10 kA breaking capacity per EN 60898, 2 MW, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1654-1KK06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1654-1KK06 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SU1654-1KK06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1654-1KK06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1654-1KK06 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SU1654-1KK06 is a 2-pole RCBO combining overcurrent protection (C-curve, 6 A rated) with a 300 mA residual-current device in a single 36 mm-wide module. It's a current-production part — no lifecycle concerns for a new BOM line.

What the ratings mean for fit

The C-curve trips between 5× and 10× In (30–60 A magnetic), which handles motor inrush and lighting loads without nuisance trips. The 300 mA residual sensitivity is for equipment protection or circuits where 30 mA would cause false trips from leakage — think water heaters, pumps, or distribution subfeeds. The 10 kA breaking capacity per EN 60898 means it can safely interrupt a fault up to that level on a 50 Hz supply. Thermal derating is published: at 40 °C ambient the continuous rating drops to 5.7 A, at 50 °C to 5.4 A, and at 70 °C to 4.62 A. If the panel runs hot, size the breaker for the actual ambient, not the 30 °C nameplate.

Panel integration and mounting

Two modular-width units (36 mm) snap onto standard DIN rail. Depth is 77 mm (70 mm installation depth), so it fits flush in most distribution boards without a deep enclosure. Supply can enter from top or bottom. Touch protection is built in — no exposed live parts when wired correctly. Rated IP20 with the distribution board installed and conductors connected — that's normal for a panel-mount device; it's not a standalone outdoor unit.

Compliance and documentation

Halogen-free and silicon-free construction, pollution degree 2, overvoltage category III. The design is instantaneous (no intentional time delay on the RCD element). Energy limitation class 3 means it limits let-through energy well in a fault — good for downstream component protection.

Frequently asked questions

Where can I buy 5SU1654-1KK06 and get current pricing?

This RCBO is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the depth of 5SU1654-1KK06?

The overall depth is 77 mm, with an installation depth of 70 mm.

What is the width of 5SU1654-1KK06?

The width is 36 mm, which corresponds to 2 modular-width units on standard DIN rail.

Will 5SU1654-1KK06 drop into a panel specified around 5SY7210-7CC without rewiring?

Both are 2-pole RCBOs on a 36 mm footprint, so the physical swap is straightforward. But the 5SU1654-1KK06 is a 6 A C-curve with 300 mA residual, while the 5SY7210-7CC is a different rating — verify the circuit's load and fault protection requirements before substituting.

What compliance documentation does Siemens provide for 5SU1654-1KK06?

The part carries EN 60898 certification for the breaking capacity rating. It is halogen-free and silicon-free, and designed to pollution degree 2 and overvoltage category III standards.

MPN