Skip to main content
Siemens 5SU1656-0KK13 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SU1656-0KK13 RCBO, 2-pole, 13 A, B-curve, 6

MPN5SU1656-0KK13

Siemens SENTRON RCBO, 2-pole (1P+N), rated 13 A at 30 °C, B-curve, 6 kA per EN 60898, 15 kA per IEC 60947-2, residual current type AC, 230/240 V AC, IP20, 2 MW, 77 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1656-0KK13 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1656-0KK13 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SU1656-0KK13 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1656-0KK13 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1656-0KK13 — Electrical
ParameterValue
Tripping Characteristic ClassB
Operational current / at AC / rated value13 A

Product details

Breaking capacity and selectivity headroom

The 5SU1656-0KK13 carries a rated short-circuit capacity of 6 kA per EN 60898 and 15 kA per IEC 60947-2. The EN 60898 value governs its use in domestic-type installations; the IEC 60947-2 value applies when the device is specified into industrial switchgear assemblies. The 15 kA figure gives useful headroom for high-fault locations without requiring an upstream current-limiting device. Energy limitation class 3 means it limits let-through energy to a low level, aiding downstream coordination.

Temperature derating — real-world current capacity

The 13 A rating is at 30 °C ambient. At 40 °C the continuous current drops to 12.48 A, at 50 °C to 11.96 A, at 60 °C to 11.31 A, and at 70 °C to 10.01 A. If the RCBO is mounted in a warm enclosure or adjacent to heat-generating devices, use the derated value for the actual ambient temperature. The device is rated for any mounting position, so orientation does not affect thermal performance.

Mounting and panel integration

The 5SU1656-0KK13 occupies 2 modular width units (36 mm) on a DIN rail. Installation depth is 70 mm, overall depth 77 mm. The supply cord can enter from either top or bottom, which simplifies wiring in tight enclosures. Protection class is IP20 once installed in a distribution board with connected conductors — the IP20 rating applies to the front face only; the rear and terminals rely on the enclosure for protection against dust and moisture.

Frequently asked questions

What is the breaking capacity of 5SU1656-0KK13?

6 kA per EN 60898 and 15 kA per IEC 60947-2.

What is the residual current type of this RCBO?

Type AC — it detects sinusoidal AC fault currents only.

Where can I buy 5SU1656-0KK13 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
5SU1656-0KK13