Skip to main content
Siemens 5SU1656-1KK13 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1656-1KK13 SENTRON RCBO, 13 A, 6 kA, Type C, 1P+N

MPN5SU1656-1KK13

Siemens SENTRON 5SU1 series RCBO, 2-pole 1P+N, 13 A rated current, tripping characteristic C, 6 kA breaking capacity (EN 60898), AC fault current type, instantaneous design, halogen-free, silicon-free, IP20, overvoltage category III, energy limiting class 3.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1656-1KK13 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1656-1KK13 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SU1656-1KK13 — Mechanical
ParameterValue
Mounting positionany
Maximum4.4 W
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1656-1KK13 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1656-1KK13 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU1656-1KK13 is a SENTRON RCBO — a combined residual-current circuit breaker with overcurrent protection — rated 13 A at AC with tripping characteristic C, breaking capacity 6 kA per EN 60898, and AC fault current sensing. It occupies 2 width units (36 mm) on a DIN rail, mounts in any position, and accepts conductors up to 35 mm² solid or stranded. This is a current-production part.

Rated current derates with ambient temperature: 13 A at 30 °C, 12.48 A at 40 °C, 12.22 A at 45 °C, 11.96 A at 50 °C, 11.57 A at 55 °C, 11.31 A at 60 °C, 10.53 A at 65 °C, and 10.01 A at 70 °C. The operating ambient range is -25 to +55 °C; storage range is -40 to +75 °C. Overvoltage category III suits fixed-installation distribution boards. The RCBO is halogen-free and silicon-free, which matters for fire-safety and contamination-sensitive environments like clean rooms or food processing.

Frequently asked questions

What is the closest functional second-source to 5SU1656-1KK13?

The closest peer listed is the 5SL6563-7BB, a Siemens RCBO with similar 1P+N form factor and tripping characteristic C. Verify the rated current and breaking capacity of the peer against your BOM before substitution.

MPN