Siemens 5SU1656-6KK40 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1656-6KK40 SENTRON RCBO, 40A Type A, B-Curve, 6kA

MPN5SU1656-6KK40
Active

Siemens SENTRON RCBO, 5SU1656-6KK40, 2-pole 1P+N, 40 A, B-curve, Type A residual current, 6 kA per EN 60898 / 10 kA per IEC 60947-2, 2 MW, halogen-free.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1656-6KK40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1656-6KK40 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SU1656-6KK40 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1656-6KK40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1656-6KK40 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

What it is and what it does

The Siemens 5SU1656-6KK40 is a SENTRON RCBO — a combined residual-current circuit breaker with overcurrent protection — rated 40 A at 30 °C, with a B-curve tripping characteristic and Type A residual-current sensitivity. It occupies 2 modular-width units (36 mm) on a DIN rail, with a depth of 77 mm and an installation depth of 70 mm. The 6 kA breaking capacity per EN 60898 (10 kA per IEC 60947-2) covers most residential and light-commercial fault levels.

Ratings that matter for panel fit

The 40 A rating derates with ambient temperature: 37.6 A at 40 °C, 36.4 A at 45 °C, 34.8 A at 50 °C, 32.4 A at 55–60 °C, 30.8 A at 65 °C, and 29.2 A at 70 °C. If your panel runs warm, size the upstream protection for the derated value, not the 30 °C headline. The 2-MW width (36 mm) and 70 mm installation depth mean it fits standard 18 mm-pitch DIN-rail enclosures without crowding adjacent breakers. Mounting position is any orientation; supply can enter from top or bottom. Halogen-free and silicon-free construction matters for environments where outgassing during a fault could damage sensitive electronics or violate clean-room specs. IP20 applies only when the distribution board is installed with connected conductors — the RCBO itself is not sealed against dust ingress in open-panel service.

Frequently asked questions

Where can I buy 5SU1656-6KK40 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate.

What is the 5SU1656-6KK40's depth and width for panel layout?

Depth is 77 mm (installation depth 70 mm), width is 36 mm (2 modular units). It fits standard 18 mm-pitch DIN-rail enclosures with no overhang.

What compliance documentation does the SENTRON 5SU1656-6KK40 carry?

It is designed to EN 60898 (6 kA) and IEC 60947-2 (10 kA), with overvoltage category III and pollution degree 2. Halogen-free and silicon-free construction are confirmed. The manufacturer provides standard CE, RoHS, and REACH declarations for the SENTRON series.