Skip to main content
Siemens 5SU1674-7AK81 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SU1674-7AK81 RCBO, 4P, 100 A, Type B, 300 m

MPN5SU1674-7AK81
Active

Siemens SENTRON RCBO, 4-pole, 100 A, Type B, 300 mA fault current, 10 kA breaking capacity, tripping characteristic C, IP20, current production.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1674-7AK81 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SU1674-7AK81 — Identification
ParameterValue
Product designationRCBO
Product design / constructionSuper resistant K
5SU1674-7AK81 — Mechanical
ParameterValue
Mounting positionany
Width in modular units11
Maximum75 °C
Minimum-40 °C
Width198 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1674-7AK81 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1674-7AK81 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

Siemens SENTRON 5SU1674-7AK81 — RCBO, 4-Pole, 100 A, Type B

The C tripping characteristic handles moderate inrush from motor or lighting loads. Supply connection can be made from either top or bottom, simplifying panel layout.

The 100 A rating is valid at 30 °C ambient. At 40 °C the continuous current derates to 92.5 A; at 50 °C to 85 A; at 60 °C to 77 A. For a panel that runs warm — say 45 °C inside the enclosure — the usable rating is 89 A. This derating curve must be factored into the load schedule for compliance with IEC 60898.

The device occupies 11 modular width units (198 mm wide), with a depth of 77 mm and a height of 90 mm. Installation depth is 70 mm. The 77 mm depth is the overall body dimension including the front face; the 70 mm installation depth is the space required behind the panel face for the body and terminals. Verify that the distribution board has sufficient gutter space for the 4-pole width and the cable bending radius for 100 A conductors.

Frequently asked questions

Where can I buy 5SU1674-7AK81 and how do I get a price?

The 5SU1674-7AK81 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 5SU1674-7AK81's listed depth (77 mm) on this component line?

The overall depth of the 5SU1674-7AK81 is 77 mm; the installation depth (space required behind the panel face) is 70 mm.

What is 5SU1674-7AK81's listed width (198 mm) on this component line?

The width is 198 mm, corresponding to 11 modular width units on a standard DIN-rail distribution board.

What compliance documentation does this brand provide for 5SU1674-7AK81 (RoHS, REACH, UL, IEC)?

The device is designed to EN 60898 and IEC 61346-2 / IEC 81346-2. It carries CE marking for the European market. RoHS and REACH compliance documentation is available from the manufacturer upon request.

MPN