The Siemens 5SU9156-7KK10 is a SENTRON RCD-operated circuit breaker — an RCBO that combines overcurrent protection and residual current detection in a single 2-module-wide (36 mm) package. The instantaneous design (no intentional time delay on the RCD element) means it trips on the first half-cycle of a residual fault — no selectivity with downstream delayed RCDs, but full speed for personnel protection.
Current derating and mounting
Rated 10 A at 30 °C ambient; derate to 9.4 A at 40 °C, 9.1 A at 45 °C, 8.7 A at 50 °C, and 8.1 A at 55 °C.