Siemens 5SU9156-7VK20 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9156-7VK20 SENTRON RCD Circuit Breaker, 20 A Type

MPN5SU9156-7VK20

Siemens SENTRON 5SU9 series, RCD-operated circuit breaker, 2-pole 1P+N, 20 A, Type A, C-curve, 6 kA (EN 60898), 10 kA (IEC 60947-2), 50 Hz, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU9156-7VK20 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9156-7VK20 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
5SU9156-7VK20 — Mechanical
ParameterValue
Mounting positionany
Maximum1.5 W
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9156-7VK20 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9156-7VK20 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU9156-7VK20 is a SENTRON RCBO — an RCD-operated circuit breaker that combines overcurrent protection and residual current detection in a single 2-module (36 mm wide) unit.

Derating that matters for panel builders

The 5SU9156-7VK20 carries a full derating table from 30 °C to 55 °C: 20 A at 30 °C, 18.8 A at 40 °C, 18.2 A at 45 °C, 17.4 A at 50 °C, and 16.2 A at 55 °C. If the distribution board ambient sits at 45 °C — common in a sealed enclosure — the usable continuous current drops to 18.2 A, so a 20 A load would nuisance-trip on a warm day. Plan the branch circuit load at the derated figure, not the label.

That 35 mm² upper end is unusual for a 20 A RCBO — it means the terminals are oversized for the rating, making daisy-chaining or looping through larger feed conductors straightforward. Strip length and torque values follow the standard SENTRON terminal spec; no special crimp lugs needed for the full range.

Mounting and clearance notes

IP20 applies when the distribution board is installed with conductors connected — exposed terminals are touch-protected per the product feature listing.

Halogen-free and silicon-free construction, which matters for installations with sensitive electronics or where low-smoke, zero-halogen cabling is specified. Energy limiting class 3, meaning it limits let-through energy well in a fault condition.

Frequently asked questions

What is the breaking capacity of the 5SU9156-7VK20?

6 kA rated value per EN 60898 for domestic-type installations, and 10 kA rated value per IEC 60947-2 for industrial panel applications.

What conductor sizes does the 5SU9156-7VK20 accept?

Solid and stranded conductors from 0.75 mm² up to 35 mm².

Where can I buy the 5SU9156-7VK20?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.