Siemens 5SU9156-7VK40 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9156-7VK40 SENTRON RCBO, 40A C-curve, 30mA Type A

MPN5SU9156-7VK40

Siemens SENTRON 5SU9 series, RCD-operated circuit breaker (RCBO), 2-pole 1P+N, 40 A rated current, C-curve, Type A fault current, 6 kA / 10 kA breaking capacity, 77 mm depth, 36 mm width (2 MW).

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU9156-7VK40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9156-7VK40 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
5SU9156-7VK40 — Mechanical
ParameterValue
Mounting positionany
Maximum1.5 W
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9156-7VK40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9156-7VK40 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU9156-7VK40 is a 2-pole (1P+N) RCBO from the SENTRON 5SU9 series — a combined overcurrent and residual-current device that fits a single 36 mm wide module (2 width units) on a DIN rail. It protects a 40 A final circuit with a C-curve magnetic trip for motor or lighting inrush and a 30 mA Type A RCD element that catches pulsating DC fault currents from electronics or variable-speed drives.

Rated current derates with ambient temperature: 40 A at 30 °C, 37.6 A at 40 °C, 36.4 A at 45 °C, 34.8 A at 50 °C, 32.4 A at 55 °C. If the panel runs at 40 °C ambient, the usable load drops to 37.6 A — a 40 A breaker on a 40 A continuous load would nuisance-trip. Terminals accept solid or stranded copper from 0.75 mm² up to 35 mm², which covers everything from a 1.5 mm² lighting circuit to a 10 mm² feeder. The 77 mm depth plus 70 mm installation depth means it clears a standard 100 mm deep enclosure back wall with room for wiring fingers.

Deployment context

Mounts on a DIN rail in any orientation — vertical, horizontal, upside-down — which simplifies layout in a tight enclosure. The IP20 rating applies only when the distribution board is installed and conductors are connected; the device itself is not sealed for washdown or outdoor use. Type A RCD detects sinusoidal AC faults plus pulsating DC up to 6 mA smooth DC superimposed — critical for circuits with half-wave rectifiers, switch-mode power supplies, or VFDs that can blind a standard AC-only RCD. If the downstream load includes a single-phase drive or LED driver, Type A is the minimum for code compliance in most jurisdictions.

Frequently asked questions

What is the breaking capacity of 5SU9156-7VK40?

6 kA per EN 60898 for distribution boards and 10 kA per IEC 60947-2 for industrial panels.

What wire sizes does the 5SU9156-7VK40 accept?

Solid or stranded copper from 0.75 mm² up to 35 mm².

Where can I buy the 5SU9156-7VK40 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the difference between the 5SU9156-7VK40 and the 5SL6563-7BB?

The 5SL6563-7BB is a standard MCB without residual-current protection, while the 5SU9156-7VK40 is an RCBO combining overcurrent and 30 mA Type A RCD protection in one module. The 5SU9156-7VK40 will not drop into a panel wired for a bare MCB without adding the RCD function — it occupies the same 2-MW footprint but requires the neutral connection for the RCD electronics.