It integrates a 6 A B-curve overcurrent trip with a 30 mA Type AC residual-current detection stage, all in a 1P+N (switched phase, solid neutral) package rated to break 10 kA per EN 60898 and IEC 60947-2. The 30 mA residual-current element provides supplementary protection against direct contact and earth faults.
Energy limitation class 3 means it lets through less let-through energy (I²t) than class 1 or 2 devices, improving downstream coordination and reducing arc-flash risk at the point of fault.
Occupies one 18 mm modular-width unit on the DIN rail. Depth is 77 mm (70 mm installation depth), height 125 mm. Mounting position is unrestricted — install in any orientation. The supply cable enters from below; a 600 mm pigtail on the neutral side simplifies wiring in pre-configured distribution boards. IP20 rating applies once the distribution board is installed and conductors are connected.